menu

logo

ELR-8V | ELR-8tcs | ELR-8mVtcs829

  • Earth leakage relay type A
  • 2 output relays each with changeover contact, configurable 2 tripping or 1 tripping and 1 alarm
  • Configurable fail safe prealarm and operation
  • Automatic toroid connection control
  • Green power LED indicator (ON)
  • Red relay tripped LED indicator (TRIP)
  • Red tripping prealarm LED indicator (ALARM)
  • Front TEST button
  • Manual resetting by front RESET button or remote contact closing
  • Automatic resetting by remote contact closing or rear jumper connection
  • Constant toroid-relay circuit control
  • Flag indicator (TRIP MEMORY) (ELR-8mVtcs only)
  • Digital fault current measurement and display with configurable tripping value memory (ELR-8mVtcs only)
  • Shunt tripping circuit operating test (TCS) (ELR-8tcs, ELR-8mVtcs only)
  • Flush mount 96x96mm housing with transparent cover
  • IEC degree of protection: IP20 terminals, IP40 on front with cover
Adjustments
Configurable tripping set-point (I∆n) 0,03...30A
30A...300A (with external multiplier CT1-M)
Prealarm set-point fixed 70%
Configurable tripping delay time (t) 0,02...0,5s | 0,2...5s
Order Code Rated Auxiliary Supply Voltage Outputs Contacts Weight (kg)
ELR-8V 48 24-48 VAC/DC 2 0,570
ELR-8V 110 110 VDC 2 0,570
ELR-8V 415 110 VAC/DC-240-415 VAC 2 0,570
ELR-8Vtcs 48 24-48 VAC/DC 2 0,570
ELR-8Vtcs 110 110 VDC 2 0,570
ELR-8Vtcs 415 110 VAC/DC-240-415 VAC 2 0,570
ELR-8mVtcs 48 24-48 VAC/DC 2 0,570
ELR-8mVtcs 110 110 VDC 2 0,570
ELR-8mVtcs 415 110 VAC/DC-240-415 VAC 2 0,570

Wiring connection (ELR-8V)

Wiring connection (ELR-8tcs and ELR-8mVtcs)

Mechanical Dimensions (mm)

Back